Stationary measurement technology PQ in class A as a top hat rail assembly.
The LINAX PQ5000 combines the characteristics of a normative energy quality measurement device with power consumption and condition monitoring functions.
The modern, multilingual design allows you to operate and parameterize the device via the website or by the high-resolution color TFT screen (800x480px). The integrated web server provides remote acquisition, visualization and analysis of measured data. No additional software is required.
Energy Quality Analysis
The device is intended to be used for a permanent assessment of power quality according to IEC 61000-4-30 Ed.3 In class A. The events recorded (voltage drop, voltage expansion, voltage interruption, RVC, current swelling, frequency change and homopolar voltage) serve both to prove that disturbances have occurred and to seek the origin of the disturbance in order to increase the safety of the supply. Using the statistical quantities of voltage and current, compliance with supply contracts or internal requirements can be verified. Assessment according to EN 50160, IEC 61000-2-2/4/12, IEEE 519, GB/T or self-defined limits can be performed after the measurement, and the corresponding compliance reports can be created by the device website (PQEasy-Report).
Product Highlights
- Independent Certification according to IEC 62586-2 by the Federal Institute of Metrology Goals
- Support for standard and manufacturer-independent PQDIF format according to IEEE 1159.3
- Set event recording duration: up to 6 seconds for samples and 3 minutes for RMS values
- Event display via website with time zoom function and values reading
- Generating reports via the device's web interface (PQ Easy Report)
- Cybersecurity (OT) / Cyber protection
- Optional SME control center: SME sensors for recording up to 100 currents via radio signal
- Average power values with Trend analysis to prevent load spikes
- Storage of the load profile with floating range (minimum/maximum) per interval
- Active energy class 0.2S, reactive energy class 0.5S (HT/LT, demand/delivery), resolution Configurable
- Additional Average Values and Meters with Selectable Base Quantity
- Technical Features
Options
Analog Outputs ±20mA (4), UPS (5x3 minutes), IEC61850, Profinet I/O
Communication
- Ethernet (Modbus/TCP, HTTP/HTTPS, NTP, SFTP, SYSLOG, REST API)
- Modbus/RTU
- Optional: IEC61850, Profinet I/O
- Automated data export (CSV and PQDIF files) for SFTP server
Cybersecurity (OT) / Cyber protection
- Function-based access authorization (RBAC)
- Secure Hypertext Transfer Protocol (https)
- Whitelist / Whitelist IEC61850 Client [Firewall]
- Audit log [Record of all manipulations]
- Sys-Log
- Secure firmware updates
- Data Logger & Uninterrupted Power Supply (UPS)
- Data Export
- PEN Test
Other Features
- 4 channels of current measurement and 4 voltage with an accuracy of 0.1%
- Measurement category 600V, Cat III (voltage), 300V, Cat III (current)
- I/O Standard: 1 digital input, 2 digital outputs
- 16 GB of data memory
- Sampling rate: 18kHz
- Monitoring and alarming by Means of limit values and monitoring functions
- For mounting the top hat rail
- Operation identical to the devices in the series SINEAX AM/DM and CENTRAX ®®
Test protocol
- Included in the delivery scope
Data Analysis
Electrotek Concepts' free PQdiffrator software can be downloaded via the link http://www.pqview.Com/pqdiffrator/ (required registration). With this software, the data of the PQDIF files can be analyzed, saved in CSV format or exported as a graph.
Digital Network Management
SMARTCOLLECT SC®2 The software can be used to build a complete ecosystem of quality and energy monitoring.
- Documentation / Downloads
- Operating Instructions (PDF | 13.1 MB)
- Flyer (PDF | 3.6 MB)
- Certified Power System Analysis (2) (PDF | 3.0 MB)
- Description of the MODBUS Interface (29) (PDF | 780.5 KB)
- IEC 61850 Interface (2) (PDF | 1.3 MB)
- IEC 61000-4-30 Ed. 3.0 Certificate of Compliance (6) (PDF | 225.0 KB)
- Declaration of Conformity IEC 61850-Modul (8) (PDF | 784.6 KB)
- Profinet Certificate (7) (PDF | 310.2 KB)
- Certificate of Conformity IEC 62053-22 (2) (PDF | 31.1 KB)
- CE Certificate (293) (PDF | 454.2 KB)
- 3D CAD files (ZIP | 10.1 MB)
- Firmware_pq5000_v3_21_11726-26.ZIP (ZIP | 163.8 MB)