A SWAS (Steam and Water Analysis System) continuously monitors the chemistry of water and steam in the cycle of thermoelectric plants, cogeneration and industrial boilers. It collects samples at various points in the cycle, adjusts pressure and temperature and sends them to online analyzers. The goal is to prevent corrosion, deposits and drag of impurities onto the turbine.
What SWAS measures
- Specific and cationic conductivity: indicate dissolved salts and contamination by leakage in the condenser.
- pH: controls the chemical treatment of the cycle.
- Dissolved oxygen: main corrosion agent in feed water.
- Silica: forms deposits on the turbine vanes.
- Sodium: detects contamination at levels of µg/L.
- Phosphate, ammonia and oxygen sequestrants: according to the treatment program.
Typical sampling points
- Desperator feeding and exit water.
- Boiler drum water (purge).
- Saturated steam, superheated and reheated steam.
- Condensed at the condenser output and after polishing.
How Conditioning Works
- Cooling: heat exchangers take the sample to about 25 °C, the analyzer reference temperature.
- Pressure reduction: valves or reduction devices bring the high pressure sample to safe levels.
- Flow control and protection: high temperature relief and cutting valves protect the analyzers.
- Distribution: the conditioned sample goes to the analyzers and to manual collection points.
How to specify
- List the sampling points with pressure, temperature and flow of each one.
- Define the parameters by point, according to the chemistry guidelines adopted by the plant.
- Dimension cooling and cooling water available.
- Choose the configuration: open panel, air-conditioned cabin or container.
- Define integration with the control system (analog or digital signals) and alarms.
See the sampling and Sample Conditioning Systems, including solutions for steam and water and for green hydrogen.
FAQ
Why measure cationic conductivity?
It removes the effect of treatment products, such as ammonia, and highlights anionic contaminants such as chloride and sulfate.
Does SWAS replace laboratory analytics?
No: It gives continuous monitoring, and laboratory analytics remains necessary for verification and calibration.