Test adapter for electrical charging points (monophasic/three-phase, type 2) to PROFITEST
Single-phase and three-phase test adapter with type 2 plug to test the effectiveness of protection measures at electrical charging points with the Profitest Master. Simulation of Fictitiously Connected Electric Vehicles and Simulation of Current Transport Capacity according to IEC 61851-1. Extended CP test pin to test charging points with permanently coupled charging cable.
- Vehicle Simulation (CP)
Vehicle states from A to E are selected with a rotary switch.
- Cable Simulation (PP)
The various encodings for loading cables with 13, 20, 32 and 63 A, As well As "unconnected cable", can be simulated with the help of a rotary switch.
- Fault Simulation
Simulation of a short circuit between CP and PE by means of a rotary switch
- Phase voltage indication via LEDs
Depending on the recharge station, one or three phases can be activated.
- Testing electrical charging stations with charging cable permanently connected by means of an extended CP test pin
For vehicle simulation (CP): States A, B, C and E can be simulated according to IEC 61851. The various Vehicle states are selected by means of a rotary switch.
- Status A – No vehicle connected
- State B – Vehicle connected but not ready for charging
- Status C – Vehicle connected and ready for loading, it is not necessary to ventilate the charging area
- Status E – Error: Short-circuit between CP and PE via internal diode
About cable simulation (PP): The various codes for charging cables with 13, 20, 32 and 63 A can be simulated. It is also possible to simulate the "no cable" state.
The various charging cables are simulated by connecting different resistances between PP and PE with the help of a rotary switch. The following values are possible according to IEC 61851:
- Without cable – 0 Ω
- Cable 13 A – 1.5 KΩ
- Cable 20 A – 680 Ω
- Cable 32 A – 220 Ω
- Cable 63 A – 100 Ω
- Documentation / Downloads
- Operating Instructions (PDF | 1.8 MB)
- Technical data (PDF | 260.0 KB)